B.2 Parameter Table
No.
Name
Selects the Stall Prevention method used to prevent
excessive current during acceleration.
Stall
0: Disabled - Motor accelerates at active acceleration
Prevention
rate. The motor may stall if load is too heavy or accel
L3-01
Selection
time is too short.
during
1: General Purpose - When output current exceeds
Acceleration
L3-02 level, acceleration stops. Acceleration will
continue when the output current level falls below the
L3-02 level.
Stall
Used when L3-01 = 1.
Prevention
100% is equal to the drive rated current.
L3-02
Level during
Decrease the set value if stalling or excessive current
Acceleration
occurs with default setting.
When using a braking resistor, use setting "0".
0: Disabled - The drive decelerates at the active
deceleration rate. If the load is too large or the
deceleration time is too short, an ov fault may occur.
Stall
1: General Purpose - The drive decelerates at the
Prevention
active deceleration rate, but if the main circuit DC bus
L3-04
Selection
voltage reaches the Stall Prevention level,
during
deceleration will stop. Deceleration will continue
Deceleration
once the DC bus level drops below the Stall
Prevention level.
4: Overexcitation Deceleration - Decelerates with the
flux level determined by n3-13 (Overexcitation
Gain).
Selects the Stall Prevention method to use to prevent
drive faults during run.
0: Disabled - Drive runs a set frequency. A heavy load
may cause the drive to trip on an oC or oL fault.
1: Decel Time 1 - The drive will decelerate at Decel
Stall
Time 1 (C1-02) if the output current exceeds the level
Prevention
set by L3-06. Once the current level drops below the
L3-05
Selection
L3-06 level, the drive will accelerate back to its
during Run
frequency reference at the active acceleration rate.
2: Decel Time 2 - Same as setting 1 except the drive
decelerates at Decel Time 2 (C1-04).
When output frequency is 6 Hz or less, Stall
Prevention during run is disabled regardless of the
setting in L3-05.
Enabled when L3-05 is set to "1" or "2". 100% is
Stall
equal to the drive rated current.
Prevention
L3-06
Decrease the set value if stalling or excessive current
Level during
occurs with the default settings.
Run
Upper level is determined by C6-01 and L8-38.
Speed
These parameters configure the multi-function output
Agreement
(H2- 01 = 2, 4, 5) settings "Speed Agree 1",
L4-01
Detection
"Frequency Detection 1," and "Frequency detection
Level
2".
226
Description
L4: Frequency Detection
Use L4 parameters to configure frequency detection operation.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
http://nicontrols.com
Range Def. Mode
0, 1
1
O
<1>
0 to 150
<2>
O
0, 1, 4
1
S
0 to 2
1
O
30 to
<2>
O
150
0.0 to
0.0
O
400.0
Hz
Addr.
Pg.
Hex
48F
490
492
493
494
499