6.3 Periodic Maintenance
Table 6.4 Performance Life Monitors Used for Component Replacement
Parameter
Component
U4-04
Cooling Fan
Main Circuit (DC bus)
U4-05
Electrolytic Capacitors
Inrush (pre-charge)
U4-06
relay
U4-07
IGBT
n
Alarm Outputs for Maintenance Monitors
An output can be set up to inform the user when a specific components has neared its expected
performance life.
When one of multi-function digital output terminals has been assigned the maintenance
monitor function (H2-oo = 2F), the terminal will close when the cooling fan, DC bus
capacitors, or DC bus pre-charge relay reach 90% of the expected performance life, or when
the IGBTs have reached 50% of their expected performance life. Additionally the digital
operator will display an alarm like shown in
that may need maintenance.
Digital Operator Alarm
Display
<1>
LT-1
<1>
LT-2
<1>
LT-3
<1>
LT-4
<2>
TrPC
<1>
This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital
outputs (H2-oo = 2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2-
oo = 10).
168
Displays the accumulated cooling fan operation time as a percentage of the
specified maintenance period (displayed in percent %).
Displays the accumulated time the capacitors are used as a percentage of the
specified maintenance period.
Displays the number of times the drive is powered up as a percentage of the
performance life of the inrush circuit.
Displays the percentage of the maintenance period reached by the IGBTs.
Table 6.5
Table 6.5 Maintenance Alarms
Function
The cooling fans have reached 90% of their
designated life time.
The DC bus capacitors have reached 90%
of their designated life time.
The DC bus charge circuit has reached
90% of its designated life time.
The IGBTs have reached 50% of their
designated life time.
The IGBTs have reached 90% of their
designated life time.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
http://nicontrols.com
Contents
to indicate the specific components
Corrective Action
Replace the cooling fan.
Contact a Yaskawa
representative or the nearest
Yaskawa sales office on
possible drive replacement.
Contact a Yaskawa
representative or the nearest
Yaskawa sales office on
possible drive replacement.
Check the load, carrier
frequency, and output
frequency.
Contact a Yaskawa
representative or the nearest
Yaskawa sales office on
possible drive replacement.