H1-oo
Function
Setting
20 to 2F External Fault
Forward Run Command
40
(2-Wire sequence)
Reverse Run Command
41
(2-Wire sequence)
61
External Search Command 1
62
External Search Command 2
67
Communications Test Mode
No.
Name
Use H2 parameters to assign functions to the multi-function digital output MA-MB-MC.
Terminal MA,
MB and MC
Refer to H2 Multi-Function Digital Output Settings
H2-01
Function
on page
Selection
(relay)
H2-01
Function
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
4
Frequency Detection 1
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
H1 Multi-Function Digital Input Selections
20: N.O., Always Detected, Ramp To Stop
21: N.C., Always Detected, Ramp To Stop
22: N.O., During Run, Ramp To Stop
23: N.C., During Run, Ramp To Stop
24: N.O., Always Detected, Coast To Stop
25: N.C., Always Detected, Coast To Stop
26: N.O., During Run, Coast To Stop
27: N.C., During Run, Coast To Stop
28: N.O., Always Detected, Fast-stop
29: N.C., Always Detected, Fast-stop
2A: N.O., During Run, Fast-stop
2B: N.C., During Run, Fast-stop
2C: N.O., Always Detected, Alarm Only (continue running)
2D: N.C., Always Detected, Alarm Only (continue running)
2E: N.O., During Run, Alarm Only (continue running)
2F: N.C., During Run, Alarm Only (continue running)
Open: Stop
Closed: Forward run
Open: Stop
Closed: Reverse run
Closed: Activates Current Detection Speed Search from the
max. output frequency (E1-04)
Closed: Activates Current Detection Speed Search from the
frequency reference
Tests the MEMOBUS/Modbus RS-422/485 interface.
Description
H2: Multi-Function Digital Output MA-MB-MC
221
for a description of setting values.
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output
Closed: Output frequency is 0
Closed: Output frequency equals the speed reference (plus or
minus 2 Hz hysteresis)
Closed: Output frequency is less than or equal to the value in
L4-01 with 2 Hz hysteresis
http://nicontrols.com
B.2 Parameter Table
Description
Range Def. Mode
0 to 13D
E
Description
Page
Addr.
Pg.
Hex
O
40B
105
Page
B
221