Main Circuit Terminal Power Supply and Motor Wiring

This section outlines the various steps, precautions, and checkpoints for wiring the main circuit
terminals and motor terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order
for the drive and motor should match. Failure to comply with proper wiring practices may cause the motor to
run in reverse if the phase order is backward.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper
application of noise filters could result in damage to the drive.
NOTICE: Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could
result in death or serious injury by fire as a result of drive damage from line voltage application to output
terminals.
n
Cable Length Between Drive and Motor
When the cable length between the drive and the motor is too long (especially at low frequency
output), note that the cable voltage drop may cause reduced motor torque. Drive output current
will increase as the leakage current from the cable increases. An increase in leakage current
may trigger an overcurrent situation and weaken the accuracy of the current detection.
Adjust the drive carrier frequency according to the following table. If the motor wiring distance
exceeds 100 m because of the system configuration, reduce the ground currents.
Refer to
Table 3.5
to set the carrier frequency to an appropriate level.
Cable Length
Carrier Frequency
Note:
When setting carrier frequency, calculate the cable length as the total distance of wiring to all connected
motors when running multiple motors from a single drive.
n
Ground Wiring
Follow the precautions to wire the ground for one drive or a series of drives.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
Recomm. Gauge
AWG, kcmil
12
14
10
Table 3.5 Cable Length Between Drive and Motor
50 m or less
15 kHz or less
http://nicontrols.com
3.6 Main Circuit Wiring
Wire Range
Screw Size
AWG, kcmil
14 to 10
14 to 10
14 to 10
M4
14 to 10
14 to 10
100 m or less
5 kHz or less
Tightening
Torque
N•m (lb.in.)
1.2 to 1.5
(10.6 to 13.3)
Greater than 100 m
2 kHz or less