B.2 Parameter Table
No.
Name
Selects the stopping method when a communication
time-out fault (CE) is detected.
Stopping
0: Ramp to stop
H5-04
Method After
1: Coast to stop
Comm. Error
2: Fast-stop
3: Alarm only
Enables or disables the communications timeout
fault (CE).
Comm. Fault
0: Disabled - A communication loss will not cause a
H5-05
Detection
communication fault.
Selection
1: Enabled - If communication is lost for more than
2 seconds, a CE fault will occur.
Drive
Set the wait time between receiving and sending
H5-06
Transmit Wait
data.
Time
Selects "request to send" (RTS) control:
RTS Control
H5-07
0: Disabled - RTS is always on.
Selection
1: Enabled - RTS turns on only when sending.
Run
Command
0: FWD/STOP, REV/STOP Method
H5-12
Method
1: RUN/STOP, FWD/REV Method
Selection
MEMOBUS
0: 0.1 Hz/1
Freq.
1: o1-03 based
H5-13
Reference and
2: 100%/30000
Freq. Monitor
3: 0.1%/1
Unit
<1>
Parameter can be changed during run.
<2>
If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
Note:
Cycle power to the drive to enable MEMOBUS/Modbus settings.
224
Description
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
http://nicontrols.com
Range Def. Mode
0 to 3
3
O
0, 1
1
O
10
10 to 65
O
ms
0, 1
1
O
0, 1
0
O
0 to 3
0
O
Addr.
Pg.
Hex
428
429
42A
42B
43D
43E