F5: Digital Output Card Settings - YASKAWA T1000A Technical Manual

Table of Contents

Advertisement

5.6 F: Option Settings
n
F4-07, F4-08: Terminal V1, V2 Signal Level
Sets the output signal level for terminals V1 and V2.
No.
F4-07
F4-08
Setting 0: 0 to 10 V
Setting 1: -10 to 10 V
u F5: Digital Output Card Settings
These parameters set up the drive for operation with the digital output option card DO-A3. This section describes
parameters that govern operation with a digital output option card. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F5-01 through F5-08: Digital Output Option Card Terminal Function Selection
When F5-09 = 2, the parameters listed in the table below are used to assign functions to the output terminals on the
option card.
No.
F5-01
Terminal P1-PC Output Selection
F5-02
Terminal P2-PC Output Selection
F5-03
Terminal P3-PC Output Selection
F5-04
Terminal P4-PC Output Selection
F5-05
Terminal P5-PC Output Selection
F5-06
Terminal P6-PC Output Selection
F5-07
Terminal M1-M2 Output Selection
F5-08
Terminal M3-M4 Output Selection
n
F5-09: DO-A3 Output Mode Selection
Determines how the DO-A3 option card is to work with the drive.
No.
F5-09
Setting 0: Separate output functions for each of 8 terminals
Setting 1: Binary output
Setting 2: Output functions assigned by F5-01 through F5-08
u F6: Communication Option Card
These parameters are to configure communication option cards and communication fault detection methods.
Some parameters apply to all communication option cards, while some parameters are used only for certain network
options.
n
F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
No.
F6-01
178
Parameter Name
Terminal V1 Signal Level
Terminal V2 Signal Level
Name
0 to 161
0 to 161
0 to 161
0 to 161
0 to 161
0 to 161
0 to 161
0 to 161
Parameter Name
DO-A3 Output Mode Selection
Parameter Name
Communications Error Operation Selection
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
Setting Range
0: During run
1: Zero speed
2: Speed agree
4: Frequency detection 1
6: Drive ready
37: During frequency output
F: Not used
F: Not used
Setting Range
0, 1
0, 1
Default
Setting Range
0 to 2
Setting Range
0 to 3
Default
0
0
Default
0
Default
1