Run the Drive using Digital Input Terminals: b1-02 = 1
This setting uses the digital input terminals to enter the run command. The factory setting is
a 2-Wire sequence.
Using a 2-Wire Sequence
Digital Input Terminals
S1
S2
Figure 4.9 Example Wiring Diagram for 2-Wire Sequence
Using a 3-Wire Sequence
When H1-05 (Multi-Function Digital Input Terminal S5 Function Selection) = 0, the functions
of terminals S1 and S2 are set to 3-Wire sequence, and the multi-function input terminal
becomes forward/reverse run command terminal.
Stop Button
(N.C.)
Figure 4.10 Example Wiring Diagram for 3-Wire Sequence Using Terminal S5
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
Forward Run
Reverse Run
Forward Run
S1
Reverse Run
S2
SC
Run Button
(N.O.)
S1
S2
S5
SC
http://nicontrols.com
ON
Drive
Digital Input Common
Drive
Run Command
Runs when S1 and S2 are closed
(Run button pushed)
Stop Command
Stops when S1 and S2 are open
(Stop button pushed)
FWD/REV Command <1>
Digital Input Common
4.5 Basic Operation
OFF
Stop
Stop