Verifying and Backing Up Parameter
Settings
Check changes to parameter settings using the Verify function.
Changes: Verify Menu on page
Save the verified parameter settings. Change the access level or set a password to the drive to
prevent accidental modification of parameter settings.
u

Parameter Access Level: A1-01

Setting the Access Level for "Operation only" (A1-01 = 0) allows the user to access parameters
A1-oo and Uo-oo only. Other parameters are not displayed.
Parameter
No.
Name
Access Level
A1-01
Selection
u

Password Settings: A1-04, A1-05

The user can set a password to the drive to restrict access. The password is selected via
parameter A1-05. The selected password must be entered in parameter A1-04 to unlock
parameter access (i.e., parameter setting A1-04 must match the value programmed into
A1-05). The following parameters cannot be viewed or edited until the value programmed
into A1-04 correctly matches the value as programmed in parameter A1-05: A1-01 and A1-03.
Note:
Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and simultaneously
depress the
u

Copy Function (Optional)

Parameter settings can be copied to another drive to simplify parameter restoration or multiple
drive setup. The RS-232C Interface Unit (Removable Type) (SI-232/JC) is required to use
the following options with J1000 drives:
n
USB/Copy Unit (JVOP-181)
The copy unit is an external option connected to the drive to copy parameter settings to another
drive. It includes a USB adapter to connect the drive to a PC.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide

4.9 Verifying and Backing Up Parameter Settings

84.
Selects which parameters are accessible via the digital operator.
0: Operation only (A1-01 and A1-04 can be set and monitored. U
parameters can be monitored)
2: Advanced Access Level (All parameters can be set and monitored)
key and the
key.
http://nicontrols.com
Refer to Verifying Parameter
Description
Setting
Default
Range
0, 2
2
4
117