Operator Programming Errors; Operator Programming Errors; Ope Codes, Causes, And Possible Solutions - YASKAWA CIMR-JC4A0002BAA Quick Start Manual

J1000 compact v/f control drive 200 v class, three-phase input: 0.1 to 5.5 kw 200 v class, single-phase input: 0.1 to 2.2 kw 400 v class, three-phase input: 0.2 to 5.5 kw
Table of Contents

Advertisement

5.6

Operator Programming Errors

An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an
individual parameter setting is inappropriate.
The drive will not operate until the parameter is set correctly; however, no alarm or fault
outputs will occur. If an oPE occurs, investigate the cause and
and Possible Solutions on page 145
u

oPE Codes, Causes, and Possible Solutions

LED Operator Display
The drive capacity setting (o2-04) and the actual capacity
of the drive are not the same.
LED Operator Display
Parameters were set outside the possible setting range.
Note: Other errors are given precedence over oPE02 when multiple errors occur at the same time.
LED Operator Display
• The same function is assigned to two multi-function
inputs.
• Excludes "Not used" and "External Fault."
The Up command was set but the Down command was not,
or vice versa (settings 10 vs. 11).
Run command for a 2-Wire sequence was set, but forward/
reverse command for a 2-Wire sequence was not.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
for the appropriate action.
Table 5.9 oPE Codes, Causes, and Possible Solutions
oPE01
Cause
oPE02
Cause
oPE03
Cause
http://nicontrols.com

5.6 Operator Programming Errors

Refer to oPE Codes, Causes,
Error Name
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Possible Solutions
Correct the value set to o2-04.
Error Name
Parameter Range Setting Error
Possible Solutions
Set parameters to the proper values.
Error Name
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function
contact inputs H1-01 to H1-05.
Possible Solutions
• Ensure all multi-function inputs are assigned to
different functions.
• Re-enter the multi-function settings to ensure this does
not occur.
Correctly set functions that need to be enabled in
combination with other functions.
Correctly set functions that need to be enabled in
combination with other functions.
5
145

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents