Cooling Fan Replacement - YASKAWA CIMR-JC4A0002BAA Quick Start Manual

J1000 compact v/f control drive 200 v class, three-phase input: 0.1 to 5.5 kw 200 v class, single-phase input: 0.1 to 2.2 kw 400 v class, three-phase input: 0.2 to 5.5 kw
Table of Contents

Advertisement

u

Cooling Fan Replacement

The cooling fan is installed on the top of the drive. The cooling fan can easily be replaced
without tools or removal of the drive or enclosure parts.
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to
comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment.
The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED
will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute
after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate
injury. Shut off the power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes
and ensure the heatsink has cooled down.
n
Removing the Cooling Fan
1.
Depress the right and left sides of the fan cover tabs and pull upward. Remove the
fan cover from the top of the drive. The following figure illustrates a drive with a single
cooling fan.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
A
B
http://nicontrols.com
6.4 Drive Cooling Fans
6
171