B.2 Parameter Table
u

b: Application

Application parameters configure the Run Command Source, DC Injection Braking, and other
application-related settings.
No.
Name
Frequency
b1-01
Reference
Selection
Run
b1-02
Command
Selection
Stopping
b1-03
Method
Selection
Reverse
b1-04
Operation
Selection
LOCAL/
b1-07
REMOTE Run
Selection
Run
Command
Selection
b1-08
while in
Programming
Mode
b1-14 Phase Order
Selection
Run
b1-17
Command at
Power Up
212
Description
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-08
1: Terminals - Analog input terminal A1
2: MEMOBUS/Modbus communications (option)
3: Potentiometer (option)
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital
operator
1: Digital input terminals
2: MEMOBUS/Modbus communications (option)
Selects the stopping method when the run command
is removed.
0: Ramp to Stop
1: Coast to Stop
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
Determines the operation when the Run command
source is switched from LOCAL to REMOTE or
between REMOTE and MEMOBUS/Modbus
communication.
0: External Run command has to be cycled at the new
source to be activated.
1: External Run command at new source is accepted
immediately.
0: Run command accepted only in the operation
menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during Run
Sets the phase order for drive output terminals U/T1,
V/T2 and W/T3.
0 : Standard
1 : Switch phase order
Determines the operation when a Run command is
active at power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
http://nicontrols.com
Addr.
Range Def. Mode
0 to 3
1
S
0 to 2
1
S
0, 1
0
S
0, 1
0
O
0, 1
0
O
0 to 2
0
O
0, 1
0
O
0, 1
0
O
Pg.
Hex
180
88
181
90
182
92
183
186
187
1C3
1C6