Wire Size and Torque Specifications
Select appropriate wire type and size from
crimp ferrules to the wire ends. Refer to
Table 3.8 Wire Size and Torque Specifications (Same for All Models)
Tightenin
Terminal Screw
g Torque
Size
MA, MB,
M3
0.5 to 0.6
MC
S1-S5,
SC, +V,
M2
0.22 to 0.25
A1, AC,
AM
n
Ferrule-Type Wire Terminations
Crimp a ferrule to signal wiring to improve wiring simplicity and reliability. Use CRIMPFOX
ZA-3, a crimping tool manufactured by PHOENIX CONTACT.
2
Size mm
(AWG)
0.25 (24)
AI 0.25-6YE
0.34 (22)
AI 0.34-6TQ
0.5 (20)
AI 0.5-6WH
0.75 (18)
AI 0.75-6GY
1.0
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
Table 3.9
Bare Wire Terminal
Tightenin
g Torque
wire size
N•m
(in-lbs)
Stranded:
0.25 to 1.5
(24 to 16)
4.4 to 5.3
Single: 0.25
to 1.5
(24 to 16)
Stranded:
0.25 to 1.0
(24 to 18)
1.9 to 2.2
Single: 0.25
to 1.5
(24 to 16)
Figure 3.12 Ferrule Dimensions
Table 3.9 Ferrule Terminal Types and Sizes
Type
L (mm)
10.5
10.5
12
12
AI 1-6RD
12
http://nicontrols.com
3.7 Control Circuit Wiring
Table
3.8. For simpler and more reliable wiring,
for ferrule terminal types and sizes.
Applic.
Recomm.
2
mm
2
mm
(AWG)
(AWG)
0.75 (18)
0.75 (18)
d1
d2
d1 (mm)
d2 (mm)
0.8
2.0
0.8
2.0
1.1
2.5
1.3
2.8
1.5
3.0
Ferrule-Type Terminal
Applic.
Recomm.
wire size
2
mm
2
mm
(AWG)
(AWG)
0.25 to 1.0
0.5 (20)
(24 to 17)
0.25 to 0.5
0.5 (20)
(24 to 20)