YASKAWA CIMR-JC4A0002BAA Quick Start Manual page 58

J1000 compact v/f control drive 200 v class, three-phase input: 0.1 to 5.5 kw 200 v class, single-phase input: 0.1 to 2.2 kw 400 v class, three-phase input: 0.2 to 5.5 kw
Table of Contents

Advertisement

A
S1
S2
S3
S4
A – Control terminal block
B – Avoid fraying wire
strands when stripping
insulation from wire.
Strip length 5.5 mm.
C – Single wire or stranded
wire
A – Drive side
B – Connect shield to ground
terminal of drive.
C – Insulation
When setting the frequency by analog reference from an external potentiometer, use shielded
twisted-pair wires and ground the shield of twisted-pair wires to the ground terminal of the
drive.
NOTICE: The analog signal lines between the drive and the operator station or peripheral equipment should
not exceed 50 meters when using an analog signal from a remote source to supply the frequency reference.
Failure to comply could result in poor system performance.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
D
S5
SC
A1
+V
AC AM AC
C
Figure 3.13 Terminal Board Wiring Guide
F
A
B
Figure 3.14 Preparing the Ends of Shielded Cables
http://nicontrols.com
3.7 Control Circuit Wiring
Preparing wire
terminal ends
B
D – Loosen screw to insert
wire.
E – Blade depth of 0.4 mm or
less
Blade width of 2.5 mm or
less
C
D
E
D – Control device side
E – Shield sheath (Insulate
with tape)
F – Shield
E
57