YASKAWA CIMR-JC4A0002BAA Quick Start Manual page 110

J1000 compact v/f control drive 200 v class, three-phase input: 0.1 to 5.5 kw 200 v class, single-phase input: 0.1 to 2.2 kw 400 v class, three-phase input: 0.2 to 5.5 kw
Table of Contents

Advertisement

L1-01
Motor Type
Setting
General-
Purpose
1
Motor
(Standard
Self-Cooled)
Drive
Dedicated
2
Motor
(Constant
Torque, 1:10)
Notes on Motor Protection
• Motor protection meeting UL and cUL standards is achieved with the motor overload
protection time (L1-02) set to factory default setting. Normally, L1-02 (Motor Overload
Protection Time) does not require setting. If the motor overload tolerance is clear, set the
overload protection time at hot start according to the motor. To detect overload earlier,
decrease the setting.
Figure 4.19
illustrates motor protection operation time characteristics.
Operation Time (minutes)
10
7
3
1
0.4
0.1
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
Table 4.12 Motor Type and Overload Tolerances
Overload Tolerance
150
Rated Speed=100% Speed
60 sec.
100
55
50
A
Continuous
D
B
0
110
100120 167 200
(60 Hz)
Speed (%)
0
100
150
Figure 4.19 Motor Protection Operation
http://nicontrols.com
4.5 Basic Operation
Cooling Ability
Motor designed to operate
from line power.
Motor cooling is most
effective when running at
rated nameplate base
frequency (check the motor
specifications).
Motor is designed to
effectively cool itself at
speeds as low as 6 Hz.
Cold Start
Hot Start
Motor Current (%)
E2-01 = 100%
200
Overload
Characteristics
Operating continuously
at less than line power
frequency can trigger
motor overload
protection (oL1). A fault
is then output and the
motor will coast to stop.
Continuous operation
with 100% load from 6
Hz to 50/60 Hz.
109
4