Table C.7 Factory Recommended Drive Branch Circuit Protection
Non-Time Delay
Class T Fuse Type
Drive Model
(Manufacturer: Ferraz)
CIMR-Jo
Rated Voltage:
600 Vac, 200 kAIR
BA0001
BA0002
BA0003
BA0006
BA0010
2A0001
2A0002
2A0004
2A0006
2A0010
2A0012
2A0020
4A0001
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
Fuse Ampere
Rating (A)
200 V Class Single-Phase Drives
A6T6
A6T10
A6T20
A6T40
A6T40
200 V Class Three-Phase Drives
A6T3
A6T6
A6T15
A6T20
A6T25
A6T25
A6T40
400 V Class Three-Phase Drives
A6T3
A6T6
A6T15
A6T20
A6T25
A6T25
A6T30
http://nicontrols.com
Fuse Type
(Manufacturer:
Bussmann)
Rated Voltage:
500 Vac, 200 kAIR
6
FWH-25A14F
10
FWH-25A14F
20
FWH-60B
40
FWH-80B
40
FWH-100B
3
FWH-25A14F
6
FWH-25A14F
15
FWH-25A14F
20
FWH-25A14F
25
FWH-70B
25
FWH-70B
40
FWH-90B
3
FWH-40B
6
FWH-40B
15
FWH-50B
20
FWH-70B
25
FWH-70B
25
FWH-90B
30
FWH-90B
C.3 UL Standards
Fuse Ampere
Rating (A)
25
25
60
80
100
25
25
25
25
70
70
90
40
40
50
70
70
90
90
251