4.5 Basic Operation
n
Switching Accel/Decel Times with Digital Input Terminals
Two acceleration / deceleration times can be selected using one of the digital input terminals
S1 through S5.
Program one of the parameters H1-01 through H1-05 to "07" (Accel/Decel Time). Opening
or closing the digital input changes the accel/decel times as shown below:
Accel/Decel Time
H1-oo = 7
Open (not selected)
Closed
n
Using S-Curve Characteristics during Acceleration/Deceleration
Use S-curve characteristics to smooth acceleration and deceleration and to minimize abrupt
shock to the load.
Note:
Setting S-curve characteristics will lengthen accel/decel times as follows:
Accel Time = Selected Accel Time + (C2-01 + C2-02)/2
Decel Time = Selected Decel Time + (C2-03 + C2-04)/2
Setting Example
Figure 4.13
illustrates S-curve characteristics switching between forward and reverse.
Forward Run
Command
Reverse Run
Command
Output
Frequency
94
Acceleration Time
C1-01
C1-03
C2-02
C2-03
C2-01
Figure 4.13 S-Curve Characteristics
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
http://nicontrols.com
C2-04
C2-01
C2-03
C2-02
Deceleration Time
C1-02
C1-04
C2-04