Motor Protection: L1-01 and L1-02

This section explains how to set motor overload protection.
n
Electronic Thermal Motor Protection
The drive has built-in electronic thermal overload protection to detect overload conditions.
This protection meets standards set by UL and cUL for motor thermal overload protection.
The protective feature is activated when the output current rises above the motor rated current
for a specified time. This speed sensitive protective feature interrupts the motor current to
protect the motor wiring and windings in the event of overload, eliminating the need for an
external overload device. When multiple motors are used with a single drive, separate overload
devices are required to properly protect the individual motor branches.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
Step
and
Gain 150%
Bias 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor value
Figure 4.18 Analog Output Gain/Bias Setting
http://nicontrols.com
4.5 Basic Operation
keys.
Bias 30%
Gain 100%
10 V
Terminal AM
output
voltage
3 V
0 V
0%
Monitor value
Display/Result
Bias 0%
Gain 100%
100%