4.5 Basic Operation
5.
Press
to select LOCAL. The LO/RE light will turn on.
6.
Press
to run the motor at 5 Hz. The RUN light will turn on.
With SW1 closed, the drive runs the motor at Multi-Step Speed 2
7.
(20 Hz).
With SW1 open and SW2 closed, the drive runs the motor at
8.
Multi-Step 3 (50 Hz).
With both SW1 and SW2 closed, the drive runs the motor at
9.
Multi-Step 4 (60 Hz).
STOP
10. Press
to stop the drive. The RUN light will flash until the
motor comes to a complete stop.
<1>
When the frequency reference is assigned to the LED operator (b1-01=0), the first step in a multi-step speed
sequence comes from d1-01.
Note:
When a run command is input from the control circuit terminal, the frequency reference value is selected
as follows:
When b1-01 = 0 and the run command is given, the drive uses the frequency set to d1-01.
When b1-01 = 1 and the run command is given, the drive uses the frequency reference value input to
analog control terminal A1.