YASKAWA CIMR-JC4A0002BAA Quick Start Manual page 188

J1000 compact v/f control drive 200 v class, three-phase input: 0.1 to 5.5 kw 200 v class, single-phase input: 0.1 to 2.2 kw 400 v class, three-phase input: 0.2 to 5.5 kw
Table of Contents

Advertisement

NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper
application of noise filters could result in damage to the drive.
A
A – Power supply
B – Drive
• Radiated Noise: Electromagnetic waves radiated from the drive and cables create noise
throughout the radio bandwidth that can affect devices.
• Induced Noise: Noise generated by electromagnetic induction can affect the signal line
and may cause the controller to malfunction.
Preventing Induced Noise
Use a noise filter on the output side or use shielded cables. Lay the cables at least 30 cm away
from the signal line to prevent induced noise.
A
MCCB
A – Power supply
B – Drive
C – Shielded motor cable
D – Motor
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
B
MCCB
R/L1
S/L2
T/L3
Figure 7.7 Output-Side Noise Filter
B
R/L1
S/L2
T/L3
Figure 7.8 Preventing Induced Noise
http://nicontrols.com
7.4 Installing Peripheral Devices
C
U/T1
1
4
V/T2
2
5
W/T3
3
6
C – Output-side noise filter
D – Motor
C
U/T1
V/T2
W/T3
E
G
E – Separate at least 30 cm
F – Controller
G – Signal line
D
D
F
187