Device Status - Hirschmann RS20 Reference Manual

Gui graphical user interface industrial ethernet (gigabit) switch
Hide thumbs Also See for RS20:
Table of Contents

Advertisement

Diagnostics
If the device is part of a redundant ring: the elimination of the reserve
redundancy (i.e. the redundancy function did actually switch on),
page 146 "Ring
the signal contact is to report the elimination of the reserve redundancy in
the redundant ring.
Default setting: no monitoring.
Note: If the device is a normal ring member and not a ring manager, it
doesn't report anything for the HIPER-Ring; for the Fast HIPER-Ring and
for MRP it only reports detected errors in the local configuration.
The elimination of the reserve redundancy for the ring/network coupling
(i.e. the redundancy function did actually switch on). Select "Monitor" for
the ring/network coupling if the signal contact is to report the elimination
of the reserve redundancy for the ring/network coupling
"Ring
Redundancy").
Default setting: no monitoring.
Note: In two-Switch coupling, both Switches must have found their
respective partners.
7.7.3

Device status

 Select the tab page "Alarm 1" or "Alarm 2" (for devices with two signal
contacts).
 In the "Mode Signal Contact" field, you select the "Device status" mode.
In this mode, the signal contact monitors the device status
page 18 "Device Status")
The device status "Error detected"
reported by means of a break in the contact via the potential-free signal
contact (relay contact, closed circuit).
202
Redundancy"). Select "Monitor" for the ring redundancy if
and thereby offers remote diagnosis.
(see on page 18 "Device Status")
7.7 Signal contact
(see on
(see on page 146
(see on
is
RM GUI L2E
Release 8.0 05/2013