Hirschmann RS20 Reference Manual page 50

Gui graphical user interface industrial ethernet (gigabit) switch
Hide thumbs Also See for RS20:
Table of Contents

Advertisement

Basic Settings
Note: When replacing a device with DIP switches, check the DIP switch
settings to ensure that they are the same.
Storing the current configuration data in the ACA:
You have the option of transferring the current device configuration,
including the SNMP password, to the ACA and the flash memory by using
the "to device" option in the "Save" frame .
Loading the Configuration file from the ACA:
When you restart the device with ACA connected, the device adopts the
configuration data from ACA and saves it permanently in the flash
memory. If the connected ACA contains invalid data, for example, if the
ACA contains an unchanged default configuration, the device loads the
data from the flash memory.
Note: Before loading the configuration data from the ACA, the device
compares the password in the device with the password in the ACA
configuration data.
The device loads the configuration data if
the admin password matches or
there is no password saved locally or
the local password is the original default password or
no configuration is saved locally.
Status
Meaning
notPresent
No ACA present
ok
The configuration data from the ACA and the device
match.
removed
The ACA was removed after booting.
notInSync
- The configuration data of the ACA and the device do
not match, or only one file exists
or
- no configuration file is present on the ACA or on the
device
outOfMemory
The local configuration data is too extensive to be
stored on the ACA.
Table 10: ACAstatus