S3-14: Torque Compensation Diminish Speed
Sets the speed level for torque compensation to diminish during the time determined by S3-15. Set as a percentage of the
maximum output frequency (E1-04). A setting of 0.0% disables this function.
No.
S3-14
S3-15: Torque Compensation Diminish Time
Sets the time for torque compensation to diminish when motor speed reaches the level set in S3-14.
No.
S3-15
S3-16: Torque Limit Reduction Time
After Position Lock at stop, S3-16 determines the length of time to reduce the torque limit rate =
No.
S3-16
S3-20: Dwell 2 Speed Reference
Sets the speed reference for the Dwell 2 function.
Note: Setting this parameter to 0.00 disables the Dwell 2 function.
No.
S3-20
Figure 42
S3-21: Dwell 2 End Speed
The Dwell 2 function will end when the drive reaches this speed. A setting of 0.00 will disable the acceleration rate switch
that occurs at the end of Dwell 2.
No.
S3-21
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Parameter Name
Torque Compensation Diminish Speed
Parameter Name
Torque Compensation Diminish Time
Parameter Name
Torque Limit Reduction Time
Parameter Name
Dwell 2 Speed Reference
Run Command
C1-07
S3-21
Figure 47 Dwell Speed Reference at Start
Parameter Name
Dwell 2 End Speed
4 Start-Up Programming & Operation
Setting Range
Setting Range
Setting Range
Setting Range
0.00 to 100.00%
ON
SFS output
Motor speed
C1-01
C2-01
S3-20
Setting Range
0.00 to 100.00%
Default
0.0 to 200.0%
0.0%
Default
0 to 5000 ms
1000 ms
Torque 300%
S3-16
Default
0 to 10000 ms
100 ms
Default
0.00%
Default
0.00%
4
97