4 Start-Up Programming & Operation
6.
The display automatically returns to the display shown in Step 3.
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 6 in "Selecting the Type of Auto-Tuning".
1.
Press
to access the motor output power parameter T1-02.
2.
Press
to view the default setting.
Press
,
,
F1
F2
3.
left
right
data in kW.
4.
Press
to save the setting.
5.
The display automatically returns to the display in Step 1.
Repeat Steps 1 through 5 to set the following parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
6.
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Speed
Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or
serious injury. Ensure the areas surrounding the drive, motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with
the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
WARNING! When performing Rotational Auto-Tuning for motor data or PG encoder offset, always uncouple the motor from the
mechanical system (remove ropes from traction sheave). Performing Rotational Auto-Tuning with the mechanical system connected to
the motor can cause hazardous situations, injury to personnel and damage to the equipment.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is applied on the load. Ensure the motor can freely spin
before beginning Auto-Tuning. Failure to comply could result in improper operation of the drive.
Enter the required information from the motor nameplate. Press
Note: These instructions continue from Step 6 in "Enter Data from the Motor Nameplate".
76
Step
Step
,
and
to enter the motor power nameplate
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
to proceed to the Auto-Tuning start display.
Display/Result
- A.TUNE -
PRG
Tuning Mode
T1-01= 0
∗0∗
Standard Tuning
ESC
FWD
DATA
Display/Result
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 3.70kW
(0.00 ~ 650.00)
"3.70kW"
ESC
FWD
DATA
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 003.70kW
(0.00 ~ 650.00)
"3.70kW"
FWD
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 004.00kW
(0.00 ~ 650.00)
"3.70kW"
FWD
Entry Accepted
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 4.00kW
(0.00 ~ 650.00)
"3.70kW"
ESC
FWD
DATA
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 4.00kW
(0.00 ~ 650.00)
"3.70kW"
ESC
FWD
DATA
- A.TUNE -
PRG
Rated Speed
T1-07= 1450RPM
(0 ~ 24000)
"1450RPM"
ESC
FWD
DATA