T1-10: Motor Rated Slip
Sets the rated slip for the motor.
The default setting displayed is the motor rated slip for a Yaskawa motor calculated from the output power set in T1-02.
Enter the data listed on the motor test report.
No.
T1-10
Parameter Settings during PM Motor Auto-Tuning: T2
The T2- parameters are used to set the Auto-Tuning input data for PM motor tuning.
T2-01: PM Auto-Tuning Mode Selection
Selects the type of Auto-Tuning to be performed.
details on different types of Auto-Tuning.
No.
T2-01
<1> Setting 12 is available in drive software versions PRG: 7017 or later.
Auto-Tuning of PG-E3 encoder characteristics requires a PG-E3 option with software version 1102 or later. To identify the PG-E3 software
version, refer to the PG-E3 labeling on the option, in the field designated "C/N" (S + four digit number).
Setting 0: Motor Data Input
Setting 1: PM Stationary Auto-Tuning
Setting 2: PM Stationary Stator Resistance Auto-Tuning
Setting 3: Initial Magnet Pole Search Parameters Auto-Tuning
Setting 4: Stationary PG Encoder Offset Auto-Tuning
Setting 10: Rotational PG Encoder Offset Auto-Tuning
Setting 11: Rotational Back EMF Constant Auto-Tuning
Setting 12: Auto-Tuning of PG-E3 Encoder Characteristics
T2-04: PM Motor Rated Power
Specifies the PM motor rated power in kilowatts.
No.
T2-04
T2-05: PM Motor Rated Voltage
Sets the PM motor rated voltage.
No.
T2-05
<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives. Multiply value by 2.875 for 600 V class drives.
T2-06: PM Motor Rated Current
Enter the PM motor rated current in amps.
No.
T2-06
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Parameter Name
Motor Rated Slip
Refer to Auto-Tuning for Permanent Magnet Motors on page 73
Parameter Name
PM Auto-Tuning Mode Selection
Parameter Name
PM Motor Rated Power
Parameter Name
PM Motor Rated Voltage
Parameter Name
PM Motor Rated Current
4 Start-Up Programming & Operation
Setting Range
0.00 to 20.00 Hz
Setting Range
0 to 4, 10 to 12
<1>
Setting Range
0.00 to 650.00 kW
Depending on o2-04
Setting Range
0.0 to 255.0 V
<1>
Setting Range
10% to 200% of the drive
rated
Depending on o2-04
current
Default
for
Default
0
Default
Default
200.0 V
<1>
4
Default
79