5 Troubleshooting
Digital Operator Display
oFA05, oFA06
,
oFA10, oFA11
,
oFA12 to oFA17
to
oFA30 to oFA43
to
oFb03 to oFb11
to
oFb12 to oFb17
to
oFC03 to oFC11
to
oFC12 to oFC17
to
134
Option Card Connection Error at Option Connector CN5-A, Option Card Fault at Option Connector
CN5-A
oFA00
Option compatibility error
Option Card Fault at Option Connector CN5-A
oFA01
Option not properly connected
Option card error occurred at option port CN5-A
Option Card Fault at Option Port CN5-B
oFb00
Option compatibility error
Option Card Fault at Option Port CN5-B
oFb01
Option not properly connected
Option Card Fault at Option Port CN5-B
oFb02
Same type of option card already connected
Option card error occurred at Option Port CN5-B
Option Card Connection Error at Option Port CN5-C
oFC00
Option compatibility error
Option Card Fault at Option Port CN5-C
oFC01
Option not properly connected
Option Card Fault at Option Port CN5-C
oFC02
A maximum of two PG option boards can be used simultaneously. Remove the PG option board
installed into option port CN5-A.
Option card error occurred at option port CN5-C
Encoder Option AD Conversion Error
oFC50
Error with the A/D conversion level (VCC level), or A/D conversion timed out.
Encoder Option Analog Circuit Error
oFC51
Incorrect signal level (+2.5 V signal)
Encoder Communication Timeout
oFC52
Signal encoder timed out waiting to receive data
Encoder Communication Data Error
oFC53
Serial encoder CRC checksum error
Encoder Error
oFC54
Alarm reading EnDat absolute position data from encoder
(OR flag from EnDat error for overvoltage, undervoltage, etc.)
Heatsink Overheat
oH
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02. Default value
for L8-02 is determined by drive capacity (o2-04).
Heatsink Overheat
oH1
The temperature of the heatsink exceeded the drive overheat level. The overheat level is determined
by drive capacity (o2-04).
Motor Overheat Alarm (PTC thermistor input)
oH3
• The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm detection level.
• Detection requires multi-function analog input H3-02 or H3-10 be set to "E".
Motor Overheat Fault (PTC thermistor input)
oH4
• The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection level.
• Detection requires that multi-function analog input H3-02 or H3-10 = "E".