YASKAWA L1000A Quick Start Manual page 79

Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

1.
After entering the data listed on the motor nameplate, press
Press
to activate Auto-Tuning. The drive begins by injecting current into the
motor for about 1 min, and then starts to rotate the motor.
2.
Note: The first digit on the display indicates which motor is undergoing Auto-Tuning
(motor 1 or motor 2). The second digit indicates the type of Auto-Tuning being
performed.
3.
Auto-Tuning finishes in approximately one to two minutes.
Parameter Settings during Induction Motor Auto-Tuning: T1
The T1- parameters are used to set the Auto-Tuning input data for induction motor tuning.
Note: For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is
complete, change E1-04, Maximum Output Frequency, to the desired value.
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used.
different types of Auto-Tuning.
No.
T1-01
Setting 0: Rotational Auto-Tuning
Setting 1: Stationary Auto-Tuning 1
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 4: Stationary Auto-Tuning 2
T1-02: Motor Rated Power
Sets the motor rated power according to the motor nameplate value.
No.
T1-02
T1-03: Motor Rated Voltage
Sets the motor rated voltage according to the motor nameplate value. Enter the motor voltage at base speed here if the
motor is operating above base speed.
Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03 for better control precision
around rated speed when using a vector control mode. The no-load voltage can usually be found in the motor test report
available from the manufacturer. If the motor test report is not available, enter approximately 90% of the rated voltage
printed on the motor nameplate. This may increase the output current and reduce the overload margin.
No.
T1-03
<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives. Multiply value by 2.875 for 600 V class drives.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Step
Refer to Auto-Tuning for Induction Motors on page 73
Parameter Name
Auto-Tuning Mode Selection
Parameter Name
Motor Rated Power
Parameter Name
Motor Rated Voltage
4 Start-Up Programming & Operation
to confirm.
Setting Range
2 (V/f)
0 to 2, 4 (OLV, CLV)
Setting Range
0.00 to 650.00 kW
Setting Range
0.0 to 255.5 V
Display/Result
- A.TUNE -
DRV
Auto-Tuning
0.00 Hz/ 0.00A
Tuning Ready ?
Press RUN key
ESC
FWD
- A.TUNE -
DRV
Rdy
Tune Proceeding
X.XX Hz/ X.XXA
FWD
- MODE -
DRV
End
Tune Successful
FWD
RESET
for details on the
Default
2 (V/f)
1 (OLV, CLV)
Default
Determined by o2-04
Default
200.0 V
<1>
<1>
77
4