7 Option Card Installation
3.
Connect one end of the ground wire (H) to the ground terminal (I) using one of the remaining screws (C). Connect
the other end of the ground wire (H) to the remaining ground terminal and installation hole on the option (B) using
the last remaining provided screw (C).
Figure 79
Note: 1. The option package includes two ground wires. Use the longer wire when plugging the option into connector CN5-C on the drive side.
Use the shorter wire when plugging the option into connector CN5-B. Refer to the option card instruction manual for more
information.
2. There are two screw holes on the drive for use as ground terminals (I). When connecting three options, two ground wires will need to
share the same drive ground terminal.
4.
Prepare and connect the wire ends as shown in
Torques on page 155
precaution to ensure that each wire is properly connected and wire insulation is not accidentally pinched into
electrical terminals.
WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose electrical connections could
result in death or serious injury by fire due to overheating electrical connections. Tightening screws beyond the specified tightening
torque may result in erroneous operation, damage to the terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not contact other wiring. Insufficient
insulation may cause a short circuit and damage the option or drive.
Figure 80
Figure 81
Preparing wire ends:
Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.
152
I
H
Figure 86 Connect the Ground Wire
to confirm that the proper tightening torque is applied to each terminal. Take particular
Shield
PG option terminal
FE/SD
B3
Figure 87 Preparing Ends of Shielded Cable
about 5.5 mm (0.22 in.)
When not using
crimped insulated
sleeves
Figure 88 Preparing and Connecting Cable Wiring
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
YEA_common
B
C
Figure 87
and
Figure
88.
Insulation
PG at motor
Ground Terminal
Shield sheath
(Insulate with electrical tape
or shrink tubing)
Screwdriver blade size
Blade depth of
0.4 mm (0.015 in.)
or less
Blade width of
2.5 mm (0.1 in.)
or less
Loosen the screws and
insert the wire into the
opening on the terminal block.
Shielded cable
(do not solder ends)
Wire Gauges and Tightening
YEA_common
Option terminal block

Advertisement