Wiring for CIMR-LU20215 to 20415, 40150 to 40605, and 50099 to 50200
• Voltage Lower Than 48 to 190 Vdc for 200 V Class Drives, 48 to 380 Vdc for 400 V Class Drives, and 48 to 500 Vdc
for 600 V Class Drives
Figure 49
Battery for DC bus
200 V Class: 48 to 190 Vdc
400 V Class: 48 to 380 Vdc
600 V Class: 48 to 500 Vdc
YEA_common
Figure 56 Using a Battery for the DC Bus and 24 V Power Supply Unit Option for the Control Circuit
(CIMR-LU20215 to 20415, 40150 to 40605, and 50099 to 50200)
<1> Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than 190 Vdc for 200 V class drives
and 380 Vdc for 400 V class drives. Failure to comply will cause the soft-charge bypass relay to remain open and result in damage to the
drive.
Refer to
Table 34
for the installation of the inrush current suppression circuit for battery.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Inrush current
suppression circuit
<1>
Inrush current suppression resistor
(A)
(D)
DC bus
power supply
(B)
L1
L2
L3
Magnetic Contactor C
Battery for
24 V
control circuit
Power
Supply
24 Vdc
Unit
H1-
= 55
(Rescue Operation)
Magnetic Contactor Sequence
Magnetic Contactor B
Magnetic Contactor A
Magnetic Contactor C
Magnetic Contactor D
H1-
= 55
(Rescue Operation)
4 Start-Up Programming & Operation
L1000A
+3
+1
Relay
R/L1
S/L2
+
T/L3
-
Power
supply
board
CN19
S3 to S12
SC
After the DC bus voltage falls lower
than the battery voltage
After the DC bus voltage is charged
to the battery voltage
Current
sensor
U/T1
V/T2
W/T3
Control
OPE
board
0.5 s
4
119