YASKAWA L1000A Quick Start Manual page 50

Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

3 Electrical Installation
Output Terminals
WARNING! Sudden Movement Hazard. The logic of terminals DM+/DM- is inverted between drive models CIMR-LA and
CIMR-LF. Check all wiring to ensure that the sequence is correct after installing the drive and connecting any other devices.
Improper wiring connections could result in death or serious injury.
Table 15
lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
output.
Note: Multi-function relay output terminals are rated at a minimum of 10 mA. If less than 10 mA is required, use the photocoupler
outputs (P1-C1, P2-C2). Using the wrong current output level may cause the output to malfunction when the terminal is activated.
Type
No.
N.O.
MA
N.C. output
Fault Relay
MB
Fault output common
MC
M1
Multi-function relay output 1 (Brake release command)
M2
Multi-Functio
M3
n Relay
Multi-function relay output 2 (Output contactor close
Output
command)
M4
<1>
M5
Multi-function relay output 3 (Drive ready)
M6
P1
Multi-Functio
Photocoupler output 1 (During Frequency output)
C1
n
Photocoupler
P2
Photocoupler output 2 (Not Used/Through Mode)
Output
C2
Analog monitor output 1 (Output speed)
FM
Monitor
Analog monitor output 2 (Output current)
AM
Output
Monitor common
AC
Safety
DM+ Safety monitor output
Monitor
Safety monitor output common
DM-
Output
<3>
<1> Refrain from assigning functions to terminals M1 thru M6 that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Connect a suppression diode as shown in
the circuit voltage.
<3> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Figure 23
48
Table 15 Control Circuit Output Terminals
Terminal Name (Function)
Figure 23
when driving a reactive load such as a relay coil. Make sure the diode rating is greater than
A
A – External power, 48 V max.
B – Suppression diode
Figure 23 Connecting a Suppression Diode
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Function (Signal Level) Default Setting
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
Contact relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
48 Vdc, 2 to 50 mA
-10 to +10 Vdc or 0 to +10 Vdc
0 V
Outputs status of Safe Disable function. Up to +48 Vdc 50
mA
B
C
YEA_common
D
C – Coil
D – 50 mA or less
<2>