Figure 37
Speed
Up/Down Command
Safe disable (terminals H1/H2 on)
or Baseblock off (H1-
= 8/9)
H2-
= 51 (Output Cont. Contr.)
H2-
= 50 (Brake Control)
Inspection Operation
Start Condition in Inspection Operation
NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference Selection Mode),
b1-01 (Speed Reference Selection), or H1-
settings, the motor may unexpectedly start running, and could result in injury.
Inspection operation is performed when an Up or Down signal is input while one of the following conditions is true:
• Parameter d1-18 is set to 0 or 3 and the selected speed is higher than d1-28 but lower than d1-29.
• Parameter d1-18 is set to 1 or 2 and a digital input programmed for Inspection Operation Speed (H1- = 54) is
enabled.
Inspection Operation uses the same acceleration characteristics and brake sequence at start as normal operation.
The carrier frequency is set to 2 kHz during Inspection Operation, but can be changed using parameter C6-21.
Stop Condition in Inspection Operation
To stop the drive during Inspection Operation, either remove the Up or Down command or reset the input terminal for
Inspection Operation.
A deceleration ramp can be set for Inspection Operation using parameter C1-15.
• If C1-15 = 0.00, the drive immediately applies the brake, shuts off the drive output, and opens the motor contactor, i.e.,
the multi-function output terminals set for "Brake Control" (H2- = 50) and "Output Contactor Control" (H2- =
51) are cleared.
• If C1-15 > 0.00, the drive decelerates to stop at the rate set to C1-15, then applies the brake, shuts the output off, and
opens the motor contactor.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Selected Speed
DC Injection Braking/
Emergency Stop
Position Lock at Start
Figure 41 With Up/Down command cleared and U1-05 < S1-26

(Multi-Function Digital Inputs). If the RUN command is on when changing any of these
4 Start-Up Programming & Operation
(DC Injection/Position
Lock Time at stop)
S1-26
Position Lock at Stop
Start Level
(Brake Close
Delay Time)
S1-05
S1-11
(Output Contactor Open
DC Injection/
Delay Time)
S1-07
Enabled
4
87