3 Electrical Installation
Figure 7
Wiring sequence should shut off
power to the drive when a fault
output is triggered.
<14>
ELCB (MCCB)
R
Three-phase
power supply
S
200 to 240 V
T
50 / 60 Hz
MC
MB
2MCCB
THRX
OFF
ON
MC
SA
MC
Braking resistor unit
Thermal relay trip contact
THRX
1
2
SA
TRX
SA
MC MA
TRX
Fault relay
contact
Multi-function
digtial inputs
(default setting)
Multi-function
analog inputs
<1> Remove the jumper when installing a DC link choke. Models CIMR-LU20085 through 20415, 40045
through 40605, and 50032 through 50200 come with a built-in DC link choke.
<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an
optional regenerative converter or dynamic braking option.
<3> Set up a thermal relay sequence to disconnect drive main power in the event of an overheat condition on the
dynamic braking option.
<4> Self-cooling motors do not require the same wiring necessary for motors with separate cooling fans.
26
Terminals -, +1, +2, B1, B2 are
for connecting options. Never
connect power supply lines to
these terminals
2MCCB
r1
s1
t1
Fuse
MC
R/L1
S/L2
T/L3
If running from a 400 V power
supply or 600 V power supply, a
step-down transformer is needed
to reduce the voltage to 200 V.
Up command / Stop
S 1
Down command / Stop
S 2
External Fault
S 3
Fault Reset
S 4
Multi-step Speed 1
S 5
Multi-step Speed 2
S 6
Multi-step Speed 3
S 7
Not Used
S 8
SN
SC
Sink / Source mode
selection wire jumper
SP
(default: Sink)
<7>
+
24 V
<8>
+
V
2 k Ω
A 1
A 2
AC
0 V
V
<8>
+
+
R
R
+
+
MEMOBUS/Modbus
S
comm. RS485/422
max. 115.2 kBps
S
IG
H 1
<10>
H 2
Safe Disable inputs
<11>
HC
Figure 6 Drive Standard Connection Diagram (example: CIMR-LU20033)
DC link choke
<1>
Thermal relay
(option)
(option)
U
U
X
X
Braking resistor
Jumper
(option)
+
+
+
+
2
1
B 1
B 2
Main Circuit
PG X3
Drive
<5>
Control Circuit
IP12
IP5
IG
Option card
CN5-C
connector
CN5-B
CN5-A
Shield ground terminal
Power supply +10.5 Vdc, max. 20 mA
Analog Input 1 (Speed Bias)
-10 to +10 Vdc (20 kΩ)
Analog Input 2 (Not used)
-10 to +10 Vdc (20 kΩ)
Power supply, -10.5 Vdc, max. 20 mA
Termination resistor
(120 Ω, 1/2 W)
DIP
Switch S2
<9>
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
<4>
FU
r1
FV
s1
M
FW
<2><3>
t1
Cooling fan
<2>
U/T1
U/T 1
V/T2
V/T 2
M
W/T3
W/T
3
Ground
TB1
<6>
A+
A
B+
PG
B
Z+
Z
SD
NC
FE
CN3
TB2
IP
IG
SG
a+
A pulse monitor signal
a-
b+
B pulse monitor signal
b-
z+
Z pulse monitor signal
z-
MA
Fault relay output
<13> <14>
250 Vac, max. 1 A
MB
30 Vdc, max 1 A
MC
(min. 5 Vdc, 10 mA)
M 1
Multi-function relay output (Brake Release Command)
250 Vac, max. 1 A
M 2
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
M 3
Multi-function relay output (Motor Contactor Close Command)
250 Vac, max. 1 A
M 4
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
M 5
Multi-function relay output (Drive Ready)
250 Vac, max. 1 A
M 6
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
P1
Photo Coupler 1
C1
(During Frequency Output)
P2
Photo Coupler 2
C2
(not used)
FM
Multi-function analog output 1
+
(Output Speed)
FM
-10 to +10 Vdc (2mA)
AM
Multi-function analog output 2
+
AC
(Output Current)
AM
-10 to +10 Vdc (2mA)
0 V
E (G)
+
+
DM
EDM (Safety Electronic Device Monitor)
DM
YEA_common
<15>
Digital output
5 to 48 Vdc
2 to 50 mA
(default setting)
<12>
shielded line
twisted-pair shielded line
control circuit terminal
main circuit terminal