C Standards Compliance
EMC Guidelines Compliance
This drive is tested according to European standards IEC/EN 61800-3: 2004, and complies with the European standards
IEC/EN 12015 (requires an optional AC reactor) and IEC/EN 12016.
Note: Make sure the protective earthing conductor complies with technical standards and local safety regulations. Because the leakage
current exceeds 3.5 mA when an EMC filter is installed, IEC/EN 61800-5-1 states that either the power supply must be
automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor with a
cross-section of at least 10 mm
EMC Filter Installation
The following conditions must be met to ensure continued compliance with European standards IEC/EN 12015 and IEC/
EN 12016.
Refer to EMC Filters on page 222
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this
drive also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
Figure 92
A – Drive
B – 10 m max cable length between drive and motor
C – Motor
5.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
WARNING! Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models CIMR-L4A0370 and larger, IEC/EN
61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing
conductor or a protective earthing conductor with a cross-section of at least 10 mm
comply may result in death or serious injury.
Figure 93
6.
Connect an AC reactor or a DC link choke to minimize harmonic distortion.
220
2
(Cu) or 16 mm
2
(Al) must be used.
for EMC filter selection.
A
U/T1
V/T2
W/T3
Figure 101 Installation Method
A – Braided shield cable
B – Metal panel
Figure 102 Ground Area
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
B
C
D
U
V
M
W
E
D – Metal conduit
E – Ground wire should be as short as possible.
2
(Cu) or 16 mm
A
C
B
C – Cable clamp (conductive)
2
(Al) must be used. Failure to