Input Terminals
Table 14
lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
input.
Type
No.
Up Command (Closed: Up, Open: Stop)
S1
Down Command (Closed: Down, Open: Stop)
S2
Multi-function input 1 (External Fault)
S3
Multi-function input 2 (Fault Reset)
S4
Multi-function input 3 (Multi-Step Speed
S5
Digital Inputs
Reference 1)
Multi-function input 4 (Multi-Step Speed
S6
Reference 2)
Multi-function input 5 (Multi-Step Speed
S7
Reference 3)
Multi-function input 6 (Not used)
S8
Multi-function input common
SC
Digital Input
0 V
SN
Power Supply
+24 Vdc
SP
Safe Disable input 1
H1
Safe Disable
Safe Disable input 2
H2
Inputs
<1>
Safe Disable function common
HC
Power supply for analog inputs
+V
Power supply for analog inputs
-V
Multi-function analog input 1 (Speed
A1
reference bias)
Analog Inputs
Multi-function analog input 2 (Not used)
A2
Analog input common
AC
E (G) Ground for shielded lines and option cards
<1> Setting jumper S3 for an external power supply makes the wire jumper between terminals H1, H2, and HC ineffective. Remove the wire jumper
and connect an external power supply that can supply terminals H1, H2, and HC continuously.
<2> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Table 14 Control Circuit Input Terminals
Terminal Name (Function)
<2>
<2>
Function (Signal Level) Default Setting
Photocoupler
24 Vdc, 8 mA
Use the wire link between terminals SC and SN or between SC
and SP to select sinking or sourcing, and to select the power
supply.
24 Vdc, 150 mA (only when DI-A3 is not used)
Use the wire jumper between terminals SC and SN or between SC
and SP to select sinking or sourcing, and to select the power
supply.
24 Vdc, 8 mA
One or both open: Drive output disabled
Both closed: Normal operation
Internal impedance: 3.3 kΩ
Off time of at least 1 ms
Set the S3 jumper to select sinking or sourcing, and to select the
power supply.
Common for the Safe Disable function
10.5 Vdc (max allowable current 20 mA)
-10.5 Vdc (max allowable current 20 mA)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
0 V
3 Electrical Installation
Page
183
54
237
234
47
3