YASKAWA L1000A Quick Start Manual page 178

Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

B Parameter Table
E2: Motor Parameters
No.
Name
E2-01
Motor Rated Current
E2-02
Motor Rated Slip
E2-03
Motor No-Load Current
E2-04
Number of Motor Poles
Motor Line-to-Line
E2-05
Resistance
E2-06
Motor Leakage Inductance
Motor Iron-Core
E2-07
Saturation Coefficient 1
Motor Iron-Core
E2-08
Saturation Coefficient 2
E2-09
Motor Mechanical Loss
Motor Iron Loss for Torque
E2-10
Compensation
E2-11
Motor Rated Power
<4> Default setting value varies by the drive model (o2-04).
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU20008 to 20033, 40005 to 40018, and
50003 to 50013 display values in 0.01 A units, while models CIMR-LU20047 to 20415, 40024 to 40605, and 50017 to 50200
display values in 0.1 A units.
176
Sets the motor nameplate full load current in Amps. Automatically set during
Auto-Tuning.
Sets the motor rated slip. Automatically set during Auto-Tuning.
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
Sets the number of motor poles. Automatically set during Auto-Tuning.
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated
voltage. Automatically set during Auto-Tuning.
Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set
during Auto-Tuning.
Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set
during Auto-Tuning.
Sets the motor mechanical loss as a percentage of motor rated power (kW).
Sets the motor iron loss.
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set during
Auto-Tuning.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Description
Setting
Default:
<4>
Min: 10% of drive
rated current
Max: 200% of
drive rated
current
<10>
Default:
<4>
Min: 0.00 Hz
Max: 20.00 Hz
Default:
<4>
Min: 0 A
Max: E2-01
<10>
Default: 4
Min: 2
Max: 48
Default:
<4>
Min: 0.000 Ω
Max: 65.000 Ω
Default:
<4>
Min: 0.0%
Max: 40.0%
Default: 0.50
Min: 0.00
Max: 0.50
Default: 0.75
Min: E2-07
Max: 0.75
Default: 0.0%
Min: 0.0%
Max: 10.0%
Default:
<4>
Min: 0 W
Max: 65535 W
Default:
<4>
Min: 0.00 kW
Max: 650.00 kW

Advertisement