C Standards Compliance
Model
CIMR-LU
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
20145
–, +1
+3
<2>
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
20180
–, +1
+3
<2>
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
20215
+3
<2>
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
20283
+3
<2>
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
20346
+3
<2>
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
20415
+3
<2>
<1> When an EMC filter is installed, additional measures must be taken in order to comply with IEC/EN 61800-5-1. Refer to
Installation on page
220.
<2> Drive models CIMR-LU20085 to 20415 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C (167°F) 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed
40°C (104°F).
226
Recommended
Terminal
AWG, kcmil
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Applicable Gauge
Gauge
AWG, kcmil
4/0
2/0 to 4/0
4/0
3/0 to 4/0
–
1 to 4/0
–
1/0 to 4/0
4
4 to 2
1/0 × 2P
1/0 to 2/0
1/0 × 2P
1/0 to 2/0
–
1 to 4/0
–
1/0 to 4/0
4
4 to 1/0
3/0 × 2P
3/0 to 300
3/0 × 2P
3/0 to 300
–
3/0 to 300
–
2 to 300
3
3 to 300
4/0 × 2P
3/0 to 300
3/0 × 2P
3/0 to 300
–
3/0 to 300
–
3/0 to 300
2
2 to 300
250 × 2P
4/0 to 600
4/0 × 2P
4/0 to 600
–
250 to 600
–
3/0 to 600
1
1 to 350
350 × 2P
250 to 600
300 × 2P
300 to 600
–
300 to 600
–
3/0 to 600
1
1 to 350
Screw
Tightening Torque
Size
Nm (lb.in.)
18 to 23
(159 to 204)
M10
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
M10
9 to 11
(79.7 to 97.4)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
EMC Filter