4 Start-Up Programming & Operation
Multi-Function Analog Outputs
The H4 parameters assign functions to analog output terminals FM and AM. Select the function for these terminals by
entering the last three digits of the desired U monitor. For a list of analog output functions, refer to
page
207.
Accel/Decel Ramp and Jerk Settings
Acceleration and deceleration ramps are set using the C1- parameters. Use the C2- parameters to adjust the jerk
at the start of acceleration or deceleration.
Figure 39
explains how accel/decel ride and jerk settings can be used to adjust the ride profile.
Figure 35
C2-02
(Jerk at
Accel End)
C2-01
(Jerk at
Accel Start)
Units used to set the acceleration and deceleration ramp as well as the Jerk function change with the setting of parameter
o1-03.
Elevator Emergency Stop
Start condition for Elevator Emergency Coast to Stop
An emergency coast to stop is performed when the Up or Down command is cleared and all of the following conditions
are met.
• Parameter b1-03 (Stopping Method Selection) is set to 4.
• Parameter d1-18 (Speed Reference Selection Mode) is set to 0 or 3.
• Parameter b1-01 (Speed Reference Selection) is set to 1.
• The Up/Down command is cleared and U1-05 (Speed Feedback) is equal to or greater than S1-26 (Emergency Stop
Start Level).
Elevator Emergency Stop Timing Chart
A timing chart for Elevator Emergency Coast to Stop and normal Ramp to Stop appears in
Figure 36
Up/Down Command
Safe disable (terminals H1/H2 on)
or Baseblock off (H1-
H2-
= 51 (Output Cont. Contr.)
H2-
= 50 (Brake Control)
86
C1-01
(Accel Ramp 1)
C1-02
(Decel Ramp 1)
Figure 39 Accel/Decel Ramp and the Jerk Function
DC Injection Braking/
Position Lock at Start
Speed
= 8/9)
Figure 40 With Up/Down command cleared and U1-05 ≥ S1-26
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
C2-03
(Jerk at
Decel Start)
C2-04
(Jerk at
C2-05 (Jerk Below Leveling Speed)
Decel End)
d1-26 (Leveling Speed)
Selected Speed
S1-26
Emergency Stop
Start Level
U: Monitors on
Figure 40
and
Figure
S1-11
(Output Contactor Open
Delay Time)
Coast to Stop
Enabled
41.