S2: Slip Compensation for Elevators
No.
Name
S2-01
Motor Rated Speed
S2-02
Slip Compensation Gain in
Motoring Mode
S2-03
Slip Compensation Gain in
Regenerative Mode
Slip Compensation Torque
S2-05
Detection Delay Time
Slip Compensation Torque
S2-06
Detection Filter Time
Constant
S3: Start/Stop Optimization
No.
Name
S3-01
Position Lock Gain at Start
1
Position Lock Gain at Start
S3-02
2
(Anti Rollback Gain)
S3-03
Position Lock Gain at Stop
S3-04
Position Lock Bandwidth
Starting Torque
S3-10
Compensation Increase
Time
Starting Torque
S3-12
Compensation Bias in
Down Direction
Torque Compensation
S3-14
Diminish Speed
Torque Compensation
S3-15
Diminish Time
Torque Limit Reduction
S3-16
Time
S3-20
Dwell 2 Speed Reference
S3-21
Dwell 2 End Speed
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Sets the motor rated speed.
Slip compensation for leveling speed can be set separately for motoring and
regenerative states. This can help improve the accuracy of leveling.
Sets a delay time before detecting torque for slip compensation.
Sets the filter time constant applied to the torque signal used for the slip compensation
value calculation.
Sets gain levels 1 and 2 for the Position Lock function. Position Lock at start attempts
to keep the car position when opening the brake in order to avoid roll back.
Sets the Position Lock gain at stop. Position Lock at stop keeps the car in position
until the brake has been applied entirely.
Determines the bandwidth around the stop position in which a digital output
programmed for "Within Position Lock Bandwidth" (H2- = 33) is closed.
Sets a time constant for the torque reference to reach 300%. Enabled by setting an
analog input terminal for torque compensation (H3- = 14).
Adds a bias to torque compensation value from the load cell when moving in the
down direction.
Sets the speed level for torque compensation to diminish during the time determined
by S3-15. Sets as a percentage of the maximum output frequency (E1-04). A setting
of 0.0% disables this function.
Sets the time for torque compensation to diminish once motor speed reaches the level
set in S3-14.
Determines the reduction rate used bring the internal torque reference value down to
zero after Position Lock at Stop has finished.
Torque 300%
Rate =
S3-16
Sets the speed reference for the Dwell 2 function.
Note: A setting of 0.00 essentially disables the Dwell 2 function.
The Dwell 2 function will end when the drive reaches this speed.
Note: A setting of 0.00 will disable the acceleration rate switch that occurs at the end
of Dwell 2.
Description
Description
B Parameter Table
Setting
Default: 1380 rpm
Min: 300 rpm
Max: 1800 rpm
Default: 0.7
Min: 0.0
Max: 5.0
Default: 1.0
Min: 0.0
Max: 5.0
Default: 1000 ms
Min: 0 ms
Max: 10000 ms
Default: 500 ms
Min: 0 ms
Max: 2000 ms
Setting
Default: 5
Min: 0
Max: 100
Default: 0.00
Min: 0.00
Max: 100.00
Default: 5
Min: 0
Max: 100
Default: 10
Min: 0
Max: 16383
Default: 500 ms
Min: 0 ms
Max: 5000 ms
Default: 0
Min: -40.0%
Max: 40.0%
Default: 0.0%
Min: 0.0%
Max: 200.0%
Default: 1000 ms
Min: 0 ms
Max: 5000 ms
Default: 100 ms
Min: 0 ms
Max: 10000 ms
Default: 0.00%
Min: 0.00%
Max: 100.00%
Default: 0.00%
Min: 0.00%
Max: 100.00%
B
201