H3: Multi-Function Analog Inputs
No.
Name
Terminal A1 Signal Level
H3-01
Selection
Terminal A1 Function
H3-02
Selection
H3-03
Terminal A1 Gain Setting
H3-04
Terminal A1 Bias Setting
Terminal A2 Signal Level
H3-09
Selection
Terminal A2 Function
H3-10
Selection
H3-11
Terminal A2 Gain Setting
H3-12
Terminal A2 Bias Setting
Analog Input Filter Time
H3-13
Constant
H3-16
Offset for Terminal A1
H3-17
Offset for Terminal A2
Setting
Function
Speed Reference Bias
(value added to input signal when
0
multiple analog terminals supply the
speed reference)
Auxiliary Speed Reference 1
2
(used as a second speed reference)
Auxiliary Speed Reference 2
3
(used as third speed reference)
E
Motor Temperature (PTC thermistor
input)
<44>
Torque Compensation (load cell
14
input)
1F
Not used (Through Mode)
<44> Available in drive software versions PRG: 7017 or later.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
0: 0 to 10 V
1: -10 to 10 V
Sets the function of terminal A1.
Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
0: 0 to 10 V
1: -10 to 10 V
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input
signal.
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10 when 10 V is input at terminal A2.
Sets the level of the input value selected in H3-10 when 0 V is input at terminal A2.
Sets a primary delay filter time constant for terminals A1 and A2. Used for noise
filtering.
Applies an offset to analog input A1. Can be used for zero adjustment of the analog
input.
Applies an offset to analog input A2. Can be used for zero adjustment of the analog
input.
H3 Multi-Function Analog Input Settings (H3-02 and H3-10)
E1-04 (maximum output frequency)
E1-04 (maximum output frequency)
E1-04 (maximum output frequency)
oH3 Alarm detection level: 1.18 V
oH4 Fault detection level: 2.293 V
10 V = Motor rated torque
Sets this value when the terminal is not used or when using the terminal in the pass-through
mode.
Description
Description (For when output is 100%)
B Parameter Table
Setting
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1F
Default: 100.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 0
Min: 0
Max: 0
Default: 0
Min: 0
Max: 1F
Default: 100.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 0.03 s
Min: 0.00 s
Max: 2.00 s
Default: 0
Min: -500
Max: 500
Default: 0
Min: -500
Max: 500
B
187