8 Communications Functions
8-6-2

Communications Commands

This section describes each command.
Command 00
Inputs forward/reverse/stop command. (To use this command, set the RUN Command Selection (A002)
to 03 (RS485).)
• Transmission Frame
Frame format
STX
STX
Control code (Start of Text)
Station
Station No. of target Inverter
No.
Command Transmission command
Data
Transmission data
BCC
Block check code
CR
Control code (Carriage Return)
* Set one of the following set values to Data.
Data
0
1
2
Example. To send the forward command to station 01
(STX) 01 00 1 (BCC) (CR) ASCII conversion 02 30 31 30 30 31 33 30 0D
• Response frame
Normal response: Refer to page 8-92
Error response: Refer to page 8-93
8 - 78
Station
Command
Data
No.
Description
Description
Stop command
Forward command
Reverse command
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
BCC
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32, and FF (Broadcast to all stations)
2 bytes
00
1 byte
Set the transmission data as shown below.*
Exclusive OR of frame segments from
2 bytes
Station No. to Data (Refer to page 8-94.)
1 byte
CR (0x0D)
Setting