• To reset a trip, perform the reset operation, or turn OFF the RUN command. (Example 1)
• If a trip is reset with the RUN command input, the inverter starts operating immediately after the trip is
reset. (Example 2)
• If the RUN command turns ON after the power supply is turned on, the inverter operates normally.
(Example 3)
• The following shows how the power recovery restart prevention function works.
(Example 1)
Power-ON with RUN command ON
(Reset with RUN command OFF)
Power supply
FW
(Forward)
USP
RS
(Reset)
Alarm
Output
frequency
Commercial Switch (CS)
• Use this function to drive a system subject to a large load inertia moment during acceleration and
deceleration with the inverter and during constant speed operation with a commercial power supply,
respectively.
• Set the Multi-function Input S1 to S8 Selection (C001 to C008) to 14 (CS).
• When the terminal CS turns ON with the RUN command input, the inverter shuts off its output. Be
sure that the output is maintained while the motor sequence is switched.
• When the terminal CS is turned from ON to OFF with the RUN command ON, after expiration of the
Restart Standby Time (b003), the inverter accelerates at the frequency according to the rotation
speed of the motor in a free-run state ("frequency matching restart"). However, the inverter may
restart at 0 Hz in any of the following cases:
The motor rotation speed is equal to or lower than 1/2 of the base rotation speed.
The motor induction voltage decreases quickly.
• When the Frequency Matching Lower Limit Frequency (b007) is set, the inverter may restart at 0 Hz if
the motor rotation speed decreases to the set frequency. (Refer to page 7-63.)
Parameter No.
C001 to C008
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
(Example 2)
Power-ON with RUN command ON
(Reset with RS)
Power supply
ON
OFF
FW
(Forward)
ON
USP
RS
(Reset)
Alarm
Output
frequency
Function name
Multi-function Input S1
14: CS (Commercial switch)
to S8 Selection
7 Detailed Functions
(Example 3)
Power-ON, then RUN command ON
(Normal operation)
Power supply
ON
FW
(Forward)
ON
USP
RS
(Reset)
Alarm
Output
frequency
Data
Default data
OFF
ON
ON
OFF
7
Unit
7 - 113