5 Basic Settings
Using an Analog Voltage Input or Analog Current Input by Switching
To switch between analog voltage and analog current inputs to set the frequency reference, set the
parameters as follows.
This enables switching between the frequency reference input (voltage reference) and frequency
reference input (current reference) terminals.
To switch between these analog input signals, use the terminal AT (Analog input switching) allocated to
a multi-function input terminal.
V
• Frequency reference input (Voltage reference), between terminal FV and FC: 0 to 9.8 VDC
• Frequency reference input (Current reference), between terminal FI and FC: 4 to 19.8 mA
Note By default, each analog input signal is set to reach the maximum frequency at 9.8 V or 19.8 mA.
Parameter No.
A001
A005
A006
C001 to C008
*1 When the terminal AT is ON, the frequency reference input (current reference) terminal is enabled.
5 - 28
A
Function name
Frequency
01: Control circuit terminal block
Reference Selection
(Analog input)
00: Switching between FV and FI via
*1
FV/FI Selection
terminal AT
FE Selection
03: FE disabled
Multi-function Input
16: Terminal AT (Analog input
S1 to S8 Selection
switching)
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Default
Data
02
00
03
Unit