Torque Control; Torque Control Parameter Settings - Omron RX Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX Series:
Table of Contents

Advertisement

6 Vector Control
6-9

Torque Control

6-9-1

Torque Control Parameter Settings

• The inverter also provides torque control, in addition to speed control and pulse train position control.
• To use this function, set the 1st Control Method (A044) to 05 (Sensor vector control) and the V2
Control Mode Selection (P012) to 00 (Speed control mode).
• To use torque control, allocate one of the Multi-function Input S1 to S8 Selection (C001 to C008) to
52 (ATR: Torque command input permission). The torque reference input is enabled when the
terminal ATR is ON.
• In the Torque Reference Input Selection (P033), select whether to input the torque reference via an
analog input terminal or the Digital Operator.
• Because, under torque control, the speed of the inverter is determined by the balance between
torque and load, set the Speed Limit Value in Torque Control (Forward/Reverse) (P039/P040) to
prevent the inverter from going out of control.
Parameter No.
P033
P034
P035
P036
P037
P038
P039
P040
C001 to C008
Related
functions
6 - 56
Function name
Torque Reference Input
Selection
Torque Reference Setting
Polarity Selection at
Torque Reference via FE
Torque Bias Mode
Torque Bias Value
Torque Bias Polarity
Selection
Speed Limit Value in
Torque Control (Forward)
Speed Limit Value in
Torque Control (Reverse)
Multi-function Input S1 to
S8 Selection
d009, d010, d012
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Data
00: Terminal FV
01: Terminal FI
02: Terminal FE
03: Digital Operator
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
Torque reference when P033 = 03
00: Signed
01: Depends on the RUN direction
00: None
01: Digital Operator
02: Terminal FE
–200. to 200. (0.4 to 55 kW)
–180. to 180. (75 to 132 kW)
Enabled when P036 = 01
00: Signed
01: Depends on the RUN direction
0.00 to 1st Maximum Frequency (A004)
0.00 to 1st Maximum Frequency (A004)
52: ATR (Torque command input
permission)
Default data
Unit
00
0.
%
00
00
0.
%
00
0.00
Hz
0.00
Hz