STOP Key Selection
• Enable/disable the STOP/RESET key on the Digital Operator or LCD Digital Operator.
• This setting is enabled when the RUN Command Selection (A002) is not set to 02 (Digital Operator).
However, when the RUN Command Selection (A002) is set to 02 (Digital Operator), the STOP/RESET
key is enabled independent of this setting.
Parameter No.
b087
STOP command via STOP/RESET
Data
00
Enabled
01
Disabled
02
Disabled
Precautions for Safe Use
• The STOP/RESET key on the Digital Operator or LCD Digital Operator is enabled only when
the STOP Key Selection parameter is set to Enabled. Be sure to provide a separate
emergency stop switch.
Stop Selection
• Select whether the motor is stopped by a deceleration stop according to the deceleration time setting
or a free-run stop, when the STOP command is input via the Digital Operator or the control circuit
terminal block.
• If the RUN command is input again during free run, the inverter will restart according to the Free-run
Stop Selection (b088) setting. (Refer to Free-run Stop Selection on page 7-98.)
Parameter No.
b091
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
00: Enabled
STOP Key Selection
01: Disabled
02: Only resetting enabled
key on Digital Operator
Function name
00: Deceleration stop
Stop Selection
01: Free-run stop
Data
Trip reset operation via
STOP/RESET key on Digital
Operator
Enabled
Disabled
Enabled
Data
7 Detailed Functions
Default data
Unit
00
Default data
Unit
00
7 - 97