(6) The extended function parameter number setting is completed.
Precautions for Correct Use
Precautions for Correct Use
If the set parameter number is not listed in the Parameter List, or if the parameter number is
hidden in the Display Selection setting, "A" in the left-end digit (4th digit) is blinking again. Refer
to Display Selection on page 7-78 to check the parameter number and set it again.
(7) Press
(Enter key) to display the parameter setting; press
key) to change the data; and press
To change the parameter setting, follow the steps (1) to (6) in a similar manner.
Returning Display to d001
Regardless of the display mode of the Digital Operator, if you press
more, the data of Output Frequency Monitor (d001) is displayed. However, the Digital Operator
continues to display the function mode and extended function mode in sequence as the normal
operation if you press the Mode key for less than 3 seconds.
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
• The parameter number "A029" is selected.
(Enter key) again to enter the new setting.
3 Operation and Test Run
/
(Increment/Decrement
(Mode key) for 3 seconds or
3
3 - 13