Operation Sequences; Servo On Function - Omron RX Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX Series:
Table of Contents

Advertisement

6-7-2

Operation Sequences

Servo ON Function

• This function is enabled when the 1st Control Method (A044) is set to 05 (Sensor vector control) to
set the motor shaft in a speed servo lock state.
Set the Multi-function Input S1 to S8 Selection (C001 to C008) to 54 (SON: Servo ON).
Once the SON function is allocated, the inverter does not accept the RUN command unless the SON
terminal turns ON.
If the SON terminal turns OFF during operation, the inverter will fall in a free-run state. In this case,
turning ON the SON terminal again causes the inverter to restart according to the Free-run Stop
Selection (b088) setting.
• Do not set the Multi-function Input S1 to S8 Selection (C001 to C008) to 55 (FOC: Preliminary
excitation).
Parameter No.
C001 to C008
b088
SON
FW (RV)
Output
Frequency
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
Multi-function Input S1 to
S8 Selection
Free-run Stop Selection
ON
ON
Speed servo-lock status
Data
54: SON (Servo ON)
55: FOC (Preliminary excitation)
00: 0-Hz restart
01: Frequency matching restart
02: Frequency pull-in restart
ON
ON
Free running Restarts according to b088.
6 Vector Control
Default data
Unit
00
ON
Does not operate because
the SON terminal is OFF.
6 - 43