7 Detailed Functions
Total Power ON Time Monitor [d017]
Use this function to display the total power ON time of the inverter.
Parameter No.
d017
Fin Temperature Monitor [d018]
Use this function to display the temperature of the cooling fin that is built into the inverter.
Parameter No.
d018
Motor Temperature Monitor [d019]
Use this function to display the temperature of the thermistor connected between the control circuit
terminals TH and SC.
Use the thermistor PB-41E (manufactured by Shibaura Electronics Co., Ltd.).
Set the Thermistor Selection (b098) to 02 (NTC enabled).
Parameter No.
d019
Life Assessment Monitor [d022]
Use this function to display the output status of each multi-function output terminal, based on whether
the corresponding 7-segment LED is lit or not lit.
This parameter can be set to display either of the following two:
• Life expectancy of main circuit board capacitor: 1
• Life expectancy of cooling fan: 2
2
7 - 8
Function name
Total Power ON Time
Monitor
Function name
Fin Temperature Monitor
Function name
Motor Temperature
Monitor
Life assessment
Normal
1
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Data
0. to 9999. (Displayed in increments of
1 hour)
1000 to 9999 (10000 to 99990)
(Displayed in increments of 10 hours)
Γ100 to Γ999 (100000 to 999000)
(Displayed in increments of 1,000 hours)
Data
–20.0 to 200.0: (Displayed in increments
of 0.1°C)
Data
–20.0 to 200.0 (Displayed in increments
of 0.1°C)
Default data
Unit
h
Default data
Unit
°C
Default data
Unit
°C