5 Basic Settings
Binary Operation
• Setting the Multi-function Input S1 to S8 Selection (C001 to C008) to 02 (CF1) to 05 (CF4) enables
the selection of the Multi-step Speed Reference 0 to 15.
• Use the Multi-step Speed Reference 1 to 15 (A021 to A035) to set the frequency for the 1st to 15th
multi-step speeds.
• For the Multi-step Speed Reference 0, set the Frequency Reference Selection (A001).
To enable the 1st/2nd/3rd frequency reference 0 setting, set A001 to 02 (Digital Operator: F001).
If this parameter is set to 01 (Control circuit terminal block: Analog input), the frequency reference for
the Multi-step Speed Reference 0 is set via analog input.
Parameter No.
C001 to
Multi-function Input S1 to S8
C008
Selection
Multi-step speed
0th
1st
2nd
3rd
4th
5th
6th
7th
8th
9th
10th
11th
12th
13th
14th
15th
• For multi-step speed binary operation, the wait time until the inverter recognizes terminal input can be
set in the Multi-step Speed/Position Determination Time (C169). This prevents the transitional status
before terminal input is recognized from being accepted.
• Input data will be determined if it remains unchanged for the time set in the Multi-step Speed/Position
Determination Time (C169). Note that setting a long determination time results in a slow input response.
Without determination time (C169)
Frequency reference
5 - 54
Function name
CF4
CF3
CF2
CF1
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
15
11
9
1
CF1
CF2
CF3
CF4
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Data
02: CF1 (Multi-step speed setting
binary 1)
03: CF2 (Multi-step speed setting
binary 2)
04: CF3 (Multi-step speed setting
binary 3)
05: CF4 (Multi-step speed setting
binary 4)
4th
5th
3rd
6th
2nd
1st
CF1
CF2
CF3
CF4
FW
13
5
4
Determination time (C169)
Default data
11th
Frequency from the
10th
Digital Operator or
12th
the external analog
9th
13th
input terminal
14th
15th
0th
7th
8th
With determination time (C169)