7 Detailed Functions
Window Comparator (Disconnection Detection FVDc/FIDc/FEDc)
• The window comparator function generates an output when the FV/FI/FV2 analog input value is
between the set upper limit and lower limit levels, enabling the analog input monitoring at the desired
level to detect a disconnection etc.
• The hysteresis width is provided for the window comparator upper/lower limit level setting.
• You can set upper and lower limit levels and a hysteresis width independently for analog input
terminals FV, FI, and FE.
• The analog input value used when the WCFV/WCFI/WCFE signal is output from an analog output
terminal can be fixed to any value. Set the Analog Operation Level at FV/FI/FE Disconnection
(b070/b071/b072). When set to no, the analog input value will be used "as is."
• The multi-function output signal FVDc/FIDc/FEDc will be output in the same way as the
WCFV/WCFI/WCFE signal, respectively.
Parameter No.
C021 to C025
C026
b060
b061
b062
b063
b064
b065
7 - 92
Function name
Multi-function Output P1
27: FVDc (Analog FV disconnection
to P5 Selection
28: FIDc (Analog FI disconnection
29: FEDc (Analog FE disconnection
Multi-function Relay
Output (MA, MB)
54: WCFV (Window comparator FV)
Function Selection
55: WCFI (Window comparator FI)
56: WCFE (Window comparator FE)
Set the upper limit level.
Window Comparator FV
Setting range: 0 to 100
Upper Limit Level
Minimum value: Lower limit level +
Hysteresis width x 2
Set the lower limit level.
Window Comparator FV
Setting range: 0. to 100.
Lower Limit Level
Maximum value: Upper limit level –
Hysteresis width x 2
Set the hysteresis width for the upper
and lower limit levels.
Window Comparator FV
Setting range: 0. to 10.
Hysteresis Width
Maximum value: (Upper limit level –
Lower limit level)/2
Set the upper limit level.
Window Comparator FI
Setting range: 0. to 100.
Upper Limit Level
Lower limit: Lower limit level +
Hysteresis width x 2
Set the lower limit level.
Window Comparator FI
Setting range: 0. to 100.
Lower Limit Level
Maximum value: Upper limit level –
Hysteresis width x 2
Set the hysteresis width for the upper
and lower limit levels.
Window Comparator FI
Setting range: 0. to 10.
Hysteresis Width
Maximum value: (Upper limit level –
Lower limit level)/2
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Data
detection)
detection)
detection)
Default data
Unit
05
100.
0.
%
100.
0.