Carrier frequency: Low
Parameter Initialization
• The parameter initialization function restores the changed parameters to the factory default settings.
• It also can clear the fault monitor data.
• As a measure to prevent inadvertent parameter initialization, the inverter is designed to force the user
to set several parameters to execute initialization.
• The following parameters are not initialized: the settings of the DriveProgramming User Parameters
U00 to U31 (P100 to P131), Total RUN Time Monitor (d016), Total Power ON Time Monitor (d017),
Initialization Data Selection (b085), Heavy Load/Light Load Selection (b049), Thermistor Adjustment
(C085), and analog adjustment parameters (C081 to C083, C121 to C123).
• If you use the 3G3RX-V1 Series Inverter for the first time or newly configure settings, execute 04
(Clear fault monitor + initialize data + Clear DriveProgramming) in b084.
• Remember that you cannot restore the initialized data to the previous settings once you execute
parameter initialization.
Parameter No.
b084
b085
b180
*1.Remember that it is impossible to undo the initialization once you press the Enter key (
parameter initialization, with the Initialization Execution (b180) set to 01.
Precautions for Correct Use
Precautions for Correct Use
The 3G3RX-V1 Series Inverter does not support the conventional initialization which is
performed by pressing multiple keys simultaneously.
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
00: Initialization disabled
01: Clear fault monitor
Initialization
02: Initialize data
Selection
03: Clear fault monitor + initialize data
04: Clear fault monitor + initialize data +
Clear DriveProgramming
Initialization Data
00: Do not change.
Selection
00: Function disabled
Initialization
*1
Execution
01: Execute initialization
7 Detailed Functions
Carrier frequency: High
Data
00
00
00
Default
Unit
data
) to execute
7 - 95
7