Omron RX Series User Manual page 341

High-function general-purpose inverter
Hide thumbs Also See for RX Series:
Table of Contents

Advertisement

Precautions for Correct Use
Precautions for Correct Use
The Output Frequency Setting/Monitor (F001) shows the frequency reference configured in the
internal memory (RAM).
F001 displays the frequency reference value selected at that time.
If you change the frequency reference value displayed in F001 and save it (by pressing the Enter
key), the data will be stored with the frequency reference selected at that time.
• For the multi-step speed reference 0, the data will be stored with the 1st Multi-step Speed
Reference 0 (A020)/2nd Multi-step Speed Reference 0 (A220)/3rd Multi-step Speed
Reference 0 (A320) according to the 1st/2nd/3rd Control Method selection.
• For the multi-step speed reference 1 to 15, the data will be stored with the corresponding
Multi-step Speed Reference 1 to 15 (A021 to A035).
* The frequency reference selection of Digital Operator (Volume adjuster), Control terminal block
(Analog input), Modbus communication, Options, DriveProgramming, and Calculation function
output cannot be changed in F001.
Acceleration/Deceleration Time Settings
• Set the motor acceleration/deceleration time. To accelerate/decelerate slowly, set a large value. To
accelerate/decelerate quickly, set a small value.
• The acceleration/deceleration time settings will be ignored and the output frequency will
instantaneously follow the reference frequency if you allocate the LAD cancel (LAC) function to one of
the multi-function input terminals and turn ON the signal for that terminal.
• To enable the switching to the 1st/2nd/3rd Acceleration Time and to the 1st/2nd/3rd Deceleration
Time, allocate one of the Multi-function Input S1 to S8 Selection to 08 (SET) or 17 (SET3) and turn
ON the terminal SET/SET3. For the multi-function input terminals, refer to Multi-function Input
Selection on page 7-108.
• Set the Acceleration/Deceleration Time Input Type (P031) to 00 (Digital Operator), 01 (Option
board 1), 02 (Option board 2), or 03 (DriveProgramming) to select the desired input type.
Parameter No.
F002
F202
F302
F003
F203
F303
P031
Related functions
*1. To enable the switching to the 2nd Acceleration Time 1/3rd Acceleration Time 1 and to the 2nd Deceleration
Time 1/3rd Deceleration Time 1, allocate one of the Multi-function Input S1 to S8 Selection (C001 to C008) to 08
(SET) or 17 (SET3) and turn ON that terminal.
*2. The default data was changed from the previous model.
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
1st Acceleration Time 1
*1
2nd Acceleration Time 1
*1
3rd Acceleration Time 1
1st Deceleration Time 1
*1
2nd Deceleration Time 1
*1
3rd Deceleration Time 1
Acceleration/Deceleration
Time Input Type
Data
Acceleration time from 0 to maximum
frequency
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
Deceleration time from maximum
frequency to 0
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
00: Digital Operator
01: Option 1
02: Option 2
03: DriveProgramming
A004, A204, A304, C001 to C008
7 Detailed Functions
Default data
Unit
*2
s
10.00
*2
s
10.00
00
7 - 15
7

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents